The addressable Control Modules FI700/M1OUT and FI700/M1REL serve for the actuation of external devices via a loop with Labor Strauss protocol. In this way fire doors, sirens or solenoid valves can be easily integrated into loop-based fire detection systems. The bi-directional communication on the loop allows for a fast actuation of the output and an accurate evaluation of the status of the module. An integrated dual-isolator disconnects the loop in case of a short circuit. In this way, the undisturbed communication with the loop elements outside the faulty loop section is ensured. The Control Module FI700/M1OUT provides one output with line-monitoring for wire breakage and short circuit and a maximum load current of 2A. An external power supply is required for the supply of the connected load device.
The Control Module FI700/M1REL comprises a dual dry change-over contact. The potential-free contacts can be used to activate ancillary devices without monitoring of the cabling.
The Module Box FI700/MBD/KO has two knockouts and is delivered with two grommets. The box allows for an easy wiring especially with surface mounted cabling.
The Module Box FI700/MB serves for the indoor surface-mounting of the module.